Basic Hardware and Function

93

6. Programming Information

System information

System information is the area which stores execution control parameters. The
following contents are included in the system information.

(1) Machine parameters (hardware type, memory type)
(2) User program information (program ID, system comments, number of steps used)
(3) Passwords
(4) Retentive register area information
(5) T1S program memory mode, 4 k steps or 8 k steps
(6) Execution control parameters (scan mode, timer interrupt interval)
(7) Station number setting for programmer port (T1), or RS-485 port communication

parameters (Enhanced model)

(8) I/O allocation table
(9) Input force table

The system information is stored in the built-in EEPROM. Therefore, when this
information is modified, the EEPROM write operation is necessary. Otherwise, these
are over-written by original EEPROM contents at the next initial load timing.

User program

The T1-16S has a capacity of 8 k steps of the user program.
The user program is stored by each program types as shown in the following diagram,
and is managed by units called blocks in each program types.

User program configuration

Program type internal configuration

(Program types)

(Blocks)

Subroutine

I/O interrupt #4

I/O interrupt #3

I/O interrupt #2

I/O interrupt #1

Timer interrupt

Sub-program #1

Block 1

Block N

(N = max. 256)

Block 10

Block 2

Block 1

Main program