beautypg.com

Troubleshooting – Toshiba 6F3B0253 User Manual

Page 291

background image

6F3B0253

Basic Hardware and Function

289

10. Troubleshooting

Error message and related information

Special

Meaning and countermeasures

Event

Info 1

Info 2

Info 3

device

Batt voltage drop

S00F

In the power-up initialization, data invalidity
of RAM (back-up area) has been detected.
If retentive registers are used, these validity
are not guaranteed. (No error down)

Boundary error

Program
type -

Address
in the

FUN No.

The register of index modification is other
than RW, T, C and D. (Error down)

block No. block

S064

The register designated by index
modification has exceeded the allowable
range. That is, out of RW, T, C and D.
(No error down)
Check the value of the index register.

Clock-calendar error

S00A

The data of built-in calendar LSI is illegal.
(No error down)
Set the date and time.
(

Enhanced model

only)

Duplicate entry No.

Program
type -
block No.

Address
in the
block

Entry No.

Multiple SUBR instructions which have the
same subroutine number are programmed.
(Error down)
Check the program.

EEPROM BCC error

Illegal
BCC

S004
S013

BCC error has been detected in the user
program of the EEPROM. (Error down)
Reload the program and execute EEPROM
write operation again.

EEPROM warning

Number
of excess
writing

S007

The number of times of writing into
EEPROM has exceeded the life (100,000
times). (No error down)
Replace the unit because the data reliability
of the EEPROM will decrease.

I/O bus error

Unit No.

Data

S005
S020

An abnormality has been detected in I/O
bus checking. (Error down)
Check the expansion cable connection and
I/O module mounting status.

I/O mismatch

Unit No. -
slot No.

Register
No.

S005
S021

The I/O allocation information and the
actual I/O configuration are not identical.
(Error down)
Check the I/O allocation and the I/O module
mounting status.

I/O no answer

Unit No. -
slot No.

Register
No.

S005
S022

No response from the T2 I/O module has
been received. (Error down)
Check the I/O allocation, the expansion
cable connection and the T2 I/O module
mounting status.

I/O parity error

Unit No. -
slot No.

Register
No.

S005
S023

I/O bus parity error has been detected in
data read/write for T2 I/O modules. (Error
down)
Check the expansion cable connection and
the T2 I/O module mounting status.

Illegal I/O reg

Unit No. -
slot No.

Register
No.

S005
S021

The allocated I/O register address exceeds
the limit, 32 words. (Error down)
Check the I/O allocation.