beautypg.com

Instructions tof off delay timer – Toshiba 6F3B0253 User Manual

Page 132

background image

6F3B0253

130

T1-16S User’s Manual

7. Instructions

TOF

OFF delay timer

Expression

Input

[ A TOF B ]

Output

Function

When the input is changed from OFF to ON, the output and the timer device corresponding to the
timer register B are set to ON. When the input is changed from ON to OFF, timer updating for B is
started. The elapsed time is stored in B. When the specified time by A has elapsed after the input
came OFF, the output and the timer device are turned OFF. (Timer updating is stopped)
The available data range for operand A is 0 to 32767.

Execution condition

Input

Operation

Output

OFF

Elapsed time

<

preset time (timer is updating)

ON

Elapsed time

preset time (timer is not updating)

OFF

ON

No operation (timer is not updating)

ON

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Preset time

0 - 32767

B Elapsed time

Example

Y021 (and the timer device T.002) is turned OFF 1 second after X000 came OFF.

X000

T002

T.002

Y021

Preset time (1 s)

Less than preset time

Preset value

Note

Time is set in 10 ms units for;

T1:

T000 to T031 (0 to 327.67 s)

T1S: T000 to T063 (0 to 327.67 s)

Time is set in 100 ms units for;

T1:

T032 to T063 (0 to 3276.7 s)

T1S: T064 to T255 (0 to 3276.7 s)

Multiple

timer

instructions

(TON,

TOF

or

SS) with the same timer register are not
allowed.