beautypg.com

Instructions fun 145 stin step sequence input – Toshiba 6F3B0253 User Manual

Page 215

background image

6F3B0253

Basic Hardware and Function

213

7. Instructions

FUN 145

STIN

Step sequence input

Expression

Input

[ STIN A ]

Output

Function

When the input is ON and the device A is ON, the output is set to ON.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

When A is ON

ON

When A is OFF

OFF

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Step device

Example

The following sequential operation is performed.
When R020 is changed from OFF to ON, R400 is set to ON and subsequent 9 devices (R401
to R409) are reset to OFF.
When X004 comes ON, R400 is reset to OFF and R401 is set to ON.
When both X005 and R022 are ON, R401 is reset to OFF and R402 is set to ON.

R020
X004
X005
R022
R400
R401
R402