7. Instructions

CPU register

T1S RS-485 port

When the instruction input is ON, one set of message (from start character to the trailing code)
which is received by the RS-485 port is read from the receive buffer, and stored in the CPU
registers. The transfer size is fixed to 256 words. The execution status and the message length
(in bytes) are stored in the status flag.
The instruction input must be kept ON until the receiving operation is complete.

Example

Source designation

Transfer size

Destination designation

D0000

H0030

D0002

00256 (fixed)

D0005

H0004

D0001

00000

D0003

Execution status

D0006

00100

D0004

Message length

T1S RS-485 port

D0100 (CPU register)

When R0000 is ON, one set of received message is read and stored in D0100 and after.

Execution status:

H0000 ... Normal complete

H0001 ... Communication error (parity error, framing error)
H0002 ... Message length over (more than 512 bytes)
H0003 ... Receive buffer over flow
H0004 ... Receive time-out (from start character to the trailing code)

Baudrate

Time-out setting

300, 600, 1200 bps

30 seconds

2400 bps

15 seconds

4800 bps

7 seconds

9600 bps

3 seconds

19200 bps

1.5 seconds

Message length: 0 .............. No receive message

1 to 512 ... Message length in bytes

Note

The XFER instruction is not executed as error in the following cases. In these cases, the

instruction error flag (ERF = S051) is set to ON. If the ERF is set to ON once, it remains ON until
resetting to OFF by user program.
(1) The leading address for the RS-485 port designation is other than 0.
(2) Transfer size is other than 256.
(3) Mode setting of the RS-485 port is not the free ASCII mode.
(4) This instruction is programmed in the sub-program #1.