beautypg.com

Instructions fun 143 wdt watchdog timer reset – Toshiba 6F3B0253 User Manual

Page 213

background image

6F3B0253

Basic Hardware and Function

211

7. Instructions

FUN 143

WDT

Watchdog timer reset

Expression

Input

[ WDT n ]

Output

Function

When the input is ON, this instruction extend the scan time over detection time by 200 ms.
Normally, T1/T1S detects the scan time-over if a scan is not finished within 200 ms. This instruction
can be used to extend the detection time.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

ON

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

n Extend time

1 - 100

Example

When R020 is ON, the scan time detection time is extended by 200 ms. The operand n has no
effect on the extended time. It is fixed as 200 ms.

Normal detection point

Extended point

0

50

100

150

200

250

300

(ms)

Extended by 200 ms

Scan

WDT instruction

execution

Note

As for the upper T-series PLCs, the operand n specifies the extended time. However in the

T1/T1S, it is fixed as 200 ms regardless of the operand n.