8. Special I/O Functions
8.3 High speed counter
8.3.1
Single phase up-counter
Function
When the count input is changed from OFF to ON, the count value is increased by 1.
When the count value reaches the set value, the count value is reset to 0, and I/O
interrupt program is activated (if the interrupt enable flag is ON). The count value is
reset to 0 when the reset input comes ON.
This counter operation is enabled while the soft-gate is ON. The count value is reset to
0 when the soft-gate is changed from ON to OFF.
The set value is set internally at the timing of the soft-gate changing from OFF to ON.
When the soft-gate is OFF, the count value can be changed by writing the data into
the set value register and setting the count preset flag to ON.
The count value range is H0000 to HFFFF (16-bit data).
Hardware condition
Count input (X000 and X001)
ON/OFF pulse width: 100
µ
s or more (max. 5KHz)
Reset input (X002 and X003)
ON/OFF duration:
2ms or more
Related registers
SW16: Function selection. Refer to section 8.1.
Function
Register/device
Remarks
Channel 1
Channel 2
Count input
X000
X001
(Note)
Reset input
X002
X003
Set value
SW18
SW20
Data range: H0000 to HFFFF
Count value
SW22
SW23
Soft-gate
S240
S248
Operation is enabled when ON
Interrupt enable
S241
S249
Interrupt is enabled when ON
Count preset
S243
S24B
Used to preset the counter value
Note) When both channels are used, X000 to X003 cannot be used as normal
input devices. However, if either one channel is used, these inputs for unused
channel can be used as normal input devices.
Interrupt assignment
Channel 1
…
I/O interrupt program #1
Channel 2
…
I/O interrupt program #2