beautypg.com

Instructions fun 024 tinz table initialize – Toshiba 6F3B0253 User Manual

Page 142

background image

6F3B0253

140

T1-16S User’s Manual

7. Instructions

FUN 024

TINZ

Table initialize

Expression

Input

[ A TINZ (n) B ]

Output

Function

When the input is ON, the data of A is stored in n registers starting with B.
The allowable range of the table size n is 1 to 1024 words.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

ON

Operand

Name

Device

Register

Constant Index

X

Y

R

S

T.

C. XW YW RW SW T

C

D

I

J

K

A Source

n Table size

1 - 1024

B Start of

destination

Example

When R010 is ON, a constant data (0) is stored in 100 registers starting with D0200 (D0200 to
D0299) and the output is turned ON.

Constant

0

D0200

0

D0201

0

D0202

0

100 registers

D0299

0