Instructions – Toshiba 6F3B0253 User Manual
Page 248

6F3B0253
246
T1-16S User’s Manual
7. Instructions
Operation mode designation (B+1):
B+1
Operation mode
Description
0
Data exchange mode
(Mode 0)
Cyclically scans the connected Inverters (Control & Monitor)
(Inverter command: P+FA01&FA00 and R+FD00&FE07)
1
Monitor mode
(Mode 1)
Cyclically scans the connected Inverters (Monitor only)
(Inverter command: R+FD00&FE07)
2
Read command mode
(Mode 2)
Sends a read command to a specified Inverter
(Inverter command: R+ User designation)
3
Write command mode
(Mode 3)
Sends a write command to a specified Inverter
(Inverter command: P+ User designation)
4
Broadcast mode
(Mode 4)
Sends a write command to all the connected Inverters as broadcast
(Inverter command: P+ User designation)
Inverter number (B):
For the operation mode 0 and 1:
It specifies the maximum Inverter number. For example, if it is 5, the T1-16S scans from #0
through #5 Inverters and repeats. Setting range is 0 to 63.
For the operation mode 2 and 3:
It specifies the target Inverter number for sending commands. Setting range is 0 to 63.
For the operation mode 4:
This setting is ignored. The broadcast address (HFF) is used as Inverter number.
Execution status (B+2):
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B+2
Communication error code (B+3):
The communication error code responded from the Inverter is shown here. If 2 or more Inverters are error,
the smallest Inverter number's error is stored. Refer to Inverter's manual for the error code.
B+3
Meaning
0
No error (Normal)
Response time-out (No answer)
Others
Inverter error response (Refer to Inverter's manual)
Inverter communication status map (B+4 to B+7):
This 4-word table shows the communication status map of each Inverter. (1: Normal / 0: Error or No
answer)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B+4
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
B+5
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
B+6
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
32
B+7
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
48
Shows the scan count.
(0
→
1
→
2
→
...
→
32767
→
0
→
1 ... )
Comes 1 when the RS-485 port is busy. (No execution)