T1-16S User’s Manual

7. Instructions

< Write command mode (Mode 3) >

When the instruction input comes ON with the operand B+1 is 3, the Write command mode
(mode 3) is selected. In this mode, the T1-16S sends the user specified Write command to the
Inverter specified by the operand B, and repeats.

Sends the specified command with command data to #n Inverter

Checks the acknowledge

The target Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command code and the command data setting registers are indirectly specified by the
operand A and A+1.

When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter.

Example

Data table designation

Parameter & status

RS-485 port

D1000

4

RW200

5

D1010

H0030 (fixed)

D1001

3010

RW201

3 (mode 3)

D1011

0 (fixed)

RW202

Execution status

RW203

Comm error code

RW204
RW205

Inverter comms

RW206

status map

RW207

When the data for each operand are set as above, the following operation condition is specified.

RW200=5

The target Inverter number is 5. Therefore T1-16S communicates with #5 Inverter.

D1000=4 & D1001=3010

D3010 is specified as the command code setting register and D3011 is

specified as the command data setting register.

Data table:

Register

Data contents

Signal direction

D3010

Command code

D3011

Command data

Write

Example operation:

For example, to write the acceleration time parameter (10 seconds) to the #5 Inverter, set the
command code H0009 into D3010 and the value 100 into D3011.
For the command code and the command data format, refer to your Inverter manual.

Repeat