10. Troubleshooting
10.1.5 Output check
If the output status monitored on the programming tool is normal but the external
output device (load) is not operated normally, check the following points:
Is the output status LED
changed ON/OFF according
No
to the program execution ?
Yes
Check the voltage between
If it is the circuit voltage at the output is
the output terminal and its
ON, or if it is 0V at the output is OFF with
common terminal.
the load ON, the T1-16S’s output circuit
It should be 0V when the
may be faulty.
output is ON, and it should
If it is 0V and the load is also OFF, check
be the circuit voltage when
the output power and the output cable
the output is OFF.
connections.
Normal
If it is not normal, check the output cable
Check the voltage at the load
connections.
If it is normal, check the specification of
the load, also check environmental factors.
Check whether the I/O
If identical, the T1-16S’s internal circuit or
allocation table is identical to
the output circuit may be faulty.
the actual I/O configuration
Not identical
Execute the automatic I/O
If it becomes identical, execute the
allocation, and check whether
EEPROM write operation.
the I/O allocation table is now
identical to the actual I/O
configuration
Still not identical
Is the allocation mismatch for
If so, the card, module or expansion unit
a specific I/O module?
may be faulty. For expansion unit, check
the expansion cable also.