8. Special I/O Functions

The table below summarizes the mode setting data of each function. In the table,

’ means do not care.

Variable input filter constant

SW16

F E D C B A 9

8 7 6

5 4 3

2 1 0

Use

1 0

− − − −

0 0

− −

0 0

− − − −

High speed counter

SW16

F E D C B A 9

8 7 6

5 4 3

2 1 0

Single phase

Channel 1 only

0 0 1 0 0 0 0 0 0 0 0 0 0 1 1

up-counter

Channel 2 only

0 1 0 0 0 0 0 0 0 0 0 0 0 1 1

Both channels

0 1 1 0 0 0 0 0 0 0 0 0 0 1 1

Single phase

Channel 1 only

0 0 1 0 1 0 0 0 0 0 0 0 0 1 1

speed-counter

Channel 2 only

0 1 0 0 1 0 0 0 0 0 0 0 0 1 1

Both channels

0 1 1 0 1 0 0 0 0 0 0 0 0 1 1

Quadrature bi-pulse counter

0 0 0 1 0 0 0 0 0 0 0 0 0 1 1

Interrupt input function

SW16

F E D C B A 9

8 7 6

5 4 3

2 1 0

Interrupt 1 only Rising (OFF to ON)

0 0 1 0 0 0 0 0 0 0 0 0 1 0 1

Falling (ON to OFF)

0 0 1 0 0 0 0 0 0 0 0 1 0 0 1

Interrupt 2 only Rising (OFF to ON)

0 1 0 0 0 0 0 0 1 0 0 0 0 0 1

Falling (ON to OFF)

0 1 0 0 0 0 0 1 0 0 0 0 0 0 1

Both interrupts No.1 = Rising, No.2 = Rising

0 1 1 0 0 0 0 0 1 0 0 0 1 0 1

1 and 2

No.1 = Rising, No.2 = Falling

0 1 1 0 0 0 0 1 0 0 0 0 1 0 1

No.1 = Falling, No.2 = Rising

0 1 1 0 0 0 0 0 1 0 0 1 0 0 1

No.1 = Falling, No.2 =
Falling

0 1 1 0 0 0 0 1 0 0 0 1 0 0 1

Pulse output function

SW26

F E D C B A 9

8 7 6

5 4 3

2 1 0

CW/CCW method

− − −

0 0 0 0 0 0 0 0 0 0 0 1 1

Pulse/Direction (PLS/DIR) method

− − −

0 0 0 0 0 0 0 0 0 0 1 1 1

PWM output function

SW26

F E D C B A 9

8 7 6

5 4 3

2 1 0

Use

− − −

0 0 0 0 0 0 0 0 0 0 0 0 1

For example, the following programs can be used to select the quadrature bi-pulse
counter.

or