Instructions, Positive pulse contact – Toshiba 6F3B0253 User Manual
Page 127

6F3B0253
Basic Hardware and Function
125
7. Instructions
P
Positive pulse contact
Expression
A
Input
P
Output
Function
When the input is ON and the device A is changed from OFF to ON (OFF at last scan and ON at
this scan), the output is turned ON.
This instruction is used to detect the device changing from OFF to ON.
Execution condition
Input
Operation
Output
OFF
Regardless of the state of device A
OFF
ON
State of device A is OFF
OFF
State of device A is ON
A is OFF at last scan
ON
A is ON at last scan
OFF
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW T
C
D
I
J
K
A Device
√
√
√
√
√
√
Example
R100 comes ON for only 1 scan when X000 is ON and X003 changes to ON.
X000
X003
R100
1 scan time
1 scan time
Note
•
The maximum usable number in a program is 2048.
(
P
N
(P)
(N)
total)