beautypg.com

IBM SCOD-3ZVQ5W User Manual

Page 518

background image

510

COG

2.

Battery output may be set to 220, 225, 230 or 240 VAC.

3.

Country-specific line cords available as options.


Notes:
1.

Data provided by Eaton.

Table 146. IBM UPS3000LV Runtimes

1

Number of Battery Packs

+0

+1

+2

+3

+4

Total Load

(Watts)

Runtime

(Hours / Minutes)

Runtime

(Hours/ Minutes)

Runtime

(Hours / Minutes)

Runtime

(Hours / Minutes)

Runtime

(Hours / Minutes)

200

1/3

5/16

7/57

11/15

14/34

300

55

4/35

7/0

9/55

12/50

400

48

4/1

6/6

8/39

11/12

500

42

3/31

5/19

7/31

9/44

600

36

3/3

4/31

6/24

8/17

700

31

2/35

3/50

5/26

7/2

800

26

2/12

3/20

4/43

6/6

900

23

1/55

2/51

4/2

5/14

1000

19

1/38

2/23

3/23

4/23

1100

16

1/22

2/4

2/56

3/48

1200

14

1/11

1/48

2/33

3/19

1300

12

1/2

1/35

2/14

2/54

1400

10

54

1/20

1/54

2/28

1500

9

46

1/11

1/41

2/10

1600

8

41

1/8

1/37

2/5

1700

8

40

1/8

1/37

2/5

1800

8

40

1/8

1/37

2/5

1900

7

39

1/0

1/25

1/50

2000

7

35

1/0

1/25

1/50

2100

7

33

1/0

1/25

1/50