Total configuration runtime estimator – IBM SCOD-3ZVQ5W User Manual
Page 516

508
COG
Notes:
1.
This table represents general guidelines for selecting the appropriate UPS based on minimum and typical
runtime estimates. A ‘maximum configuration’ load will result in ‘minimum’ UPS runtime. ‘Typical’
loads are based on a production system running at approximately 70% of maximum capacity (based on
the power delivered to the device from the power source, i.e., 70% of the value provided as a maximum
equals the rating of the power supply). The ‘typical’ loads represent a more likely configuration;
therefore, they provide a more likely estimate of runtime. The values listed as typical generally are equal
to the rating of the power supply. Since power supplies operate at 70% of load, the system power
supplies are actually operating at 70% of the values listed, though the power required from the source is
what is listed. Customer environments are unique and are unlikely to be precisely represented by any of
the specific entries in the table.
2.
Power-Factor Corrected (PFC) power supply.
3.
Use with IBM UPS7500X or UPS10000X only.
Total Configuration runtime estimator
DS4100 Disk System (1724100)
2
2/2
275/390
DS4300 Disk System (172260U)
2
2/2
390/557
DS4400 Disk System (17421RU)
2
2/2
275/390
DS4500 Disk System (174290U)
2
2/2
275/390
DS4000 EXP100 Storage Expansion Unit (171010U)
2
2/2
245/350
SAN Fibre Channel Switch, 16-Port (2005H16)
2/2
140/200
Table 144. IBM UPS750T, 1000T, 1500T Runtimes
1
Tower
UPS750T
UPS1000T
UPS1500T
Total Load (Watts)
Runtime (Minutes)
Runtime (Minutes)
Runtime (Minutes)
50
105
224
269
100
57
127
157
200
28
64
80
300
18
41
51
400
13
29
37
500
10
23
28
600
--
18
22
700
--
15
18
800
--
12
15
900
--
11
13
1000
--
9
11
1200
--
--
9
1400
--
--
7
Table 143. Power Load Data (continued)
Server
Number of Power Cords (Std/Max)
Watts Load
(Typical/Max)
1