LUBRICATION

12

Change oil after the first 5 op­

erating hours, every 25 hours of

operation thereafter. Remove oil

drain plug and drain oil while

engine is warm. Reinstall drain

plug. Remove dipstick and fill

engine crankcase with new oil of

proper grade. Use same grade of

oil in OIL MAKE-UP TANK as was

used in crankcase. Crankcase oil

capacity is approximately 3,5 pints

(1,65 liters).

GENERAL

OIL RECOMMENDATIONS

Use any high quality detergent oil

having a classification that in­

cludes SC, SD or SE, as recommend­

ed in CHART at right. No special

additives should be used.

RECOMMENDED SAE VISCOSITY GRADES

mmmmi

' 10W-30, 10W-40

I

I

op-20

20

40

60

80

’C-30

-20

10

10

20

30

100

—S-

40

TEMPERATURE RANGE ANTICIPATED BEFORE NEXT QILCHANGE

*If not available, a synthetic oil may be used having

5W-20, 5W-30 or 5W-40 viscosity.

#

OIL FILL AND DIPSTICK

A plastic oil fill tube is used,

with the bottom of the tube press­

ed into a rubber grommet and seal­

ed, A leak at the base of the. tube

or in the dipstick seal can cause

loss of crankcase Vacuum, This, in

turn,

will

result

in

smoke

discha­

rge from the exhaust and failure

of the oil make-up system to func­

tion,

CRANKCASE BREATHERS

The crankcase breathers act to maintain a partial vacuum in the crank­

case, This vacuum, prevents oil from being forced out at the rings, oil

seals, and gaskets.

Issued 4-78