Either of 2 Sensing Transformers may be used. I4ien checking Transform­

er windings for an open condition, resistance readings obtained should

be as shown in the following CHART:

TEST 37 -

SENSING TRANSFORMER

TRANSFORMER

MAKE

RESIS.TANCE [in OHMS)

Primary

Secondary

WesCoil

CoilTran

745-825

824-1114

1603 - 2169

1222 - 1654

A.) Remove wire nuts that retain

wires

#11

and #

22

, between the

Transformer and Voltage Regulator

Disconnect the wires. Set VOM to

”+DC’ and to ’’RxlOO” scale. Zero

the meter. Connect one meter test

probe to Wire #11, and the second

test probe to Wire #22. Meter

needle should swing upscale and

indicate resistance for SECONDARY

winding.

Sensing
Transformer
With Wires To
Secondary
Winding

White ' Pin No. 5

Receptacle

Pins No. 3 and
No. 5 to Primary

Winding of
Transformer ---------------

RESULTS: 1.) Checks Good.

2,) Checks Bad..

Continue

tes.ts

in

"Diagnos­

tic Flow Charts", Section 3

.Replace Sensing Transformer

B. ) Set VOM to "+DC" and to "Rxl0,000" scale. Zero the meter. Connect

one meter test probe to Wire #11. Connect the second test probe to

Ground. Meter needle should NOT move. Any needle movement indicates a

shorted condition.

RESULTS: 1.) Tests Good................................................................... Continue tests in "Diag­

nostic Flow Charts"

2.) Tests Bad...................................................................Replace Transformer

C. ) Unplug the white connector plug from its receptacle. Set the VOM

to "+DC" and to "RxlOO" scale. Zero the meter. Connect one meter test

probe to White receptacle Pin #3. Connect the second test probe to

white receptacle Pin #5. Meter needle should swing upscale and indic­

ate resistance shown in CHART for PRIMARY winding,

RESULTS: 1.) Tests Good......................................................Continue tests in "Diagnostic

Flow Charts", Section 3

2.) Tests Bad................................................... Replace Transformer

D. ) Set VOM to "+DC" and to "Rxl0,000" scade. Zero the meter. Connect

one meter test probe to white receptacle Pin #3. Connect the remain­

ing test probe to Ground. .Meter.needle should not move.Any movement

of the needle indicates a shorted condition.

RESULTS. 1.) Tests Good......................................................Continue tests in "Diagnostic

Flow Charts", Section 3

2.) Tests Bad.................................................... Replace Transformer