Test 37 – Generac Power Systems TXP User Manual
Page 41
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Either of 2 Sensing Transformers may be used. I4ien checking Transform
er windings for an open condition, resistance readings obtained should
be as shown in the following CHART:
TEST 37 -
SENSING TRANSFORMER
TRANSFORMER
MAKE
RESIS.TANCE [in OHMS)
Primary
Secondary
WesCoil
CoilTran
745-825
824-1114
1603 - 2169
1222 - 1654
A.) Remove wire nuts that retain
wires
#11
and #
22
, between the
Transformer and Voltage Regulator
Disconnect the wires. Set VOM to
”+DC’ and to ’’RxlOO” scale. Zero
the meter. Connect one meter test
probe to Wire #11, and the second
test probe to Wire #22. Meter
needle should swing upscale and
indicate resistance for SECONDARY
winding.
Sensing
Transformer
With Wires To
Secondary
Winding
White ' Pin No. 5
Receptacle
Pins No. 3 and
No. 5 to Primary
Winding of
Transformer ---------------
RESULTS: 1.) Checks Good.
2,) Checks Bad..
Continue
tes.ts
in
"Diagnos
tic Flow Charts", Section 3
.Replace Sensing Transformer
B. ) Set VOM to "+DC" and to "Rxl0,000" scale. Zero the meter. Connect
one meter test probe to Wire #11. Connect the second test probe to
Ground. Meter needle should NOT move. Any needle movement indicates a
shorted condition.
RESULTS: 1.) Tests Good................................................................... Continue tests in "Diag
nostic Flow Charts"
2.) Tests Bad...................................................................Replace Transformer
C. ) Unplug the white connector plug from its receptacle. Set the VOM
to "+DC" and to "RxlOO" scale. Zero the meter. Connect one meter test
probe to White receptacle Pin #3. Connect the second test probe to
white receptacle Pin #5. Meter needle should swing upscale and indic
ate resistance shown in CHART for PRIMARY winding,
RESULTS: 1.) Tests Good......................................................Continue tests in "Diagnostic
Flow Charts", Section 3
2.) Tests Bad................................................... Replace Transformer
D. ) Set VOM to "+DC" and to "Rxl0,000" scade. Zero the meter. Connect
one meter test probe to white receptacle Pin #3. Connect the remain
ing test probe to Ground. .Meter.needle should not move.Any movement
of the needle indicates a shorted condition.
RESULTS. 1.) Tests Good......................................................Continue tests in "Diagnostic
Flow Charts", Section 3
2.) Tests Bad.................................................... Replace Transformer
4o20
Issued
6-78