CONTROL PANEL

5

CUSTOMER WIRING CONNECTIONS

Customer wiring connections for

120

volts only are shown at right.

A 3-wire cable should be used.

Connect two alternator T2 wires to

one cable wire. Connect one alter­

nator Tl'wire to a second cable

wire. The third cable wire should'

be connected to the grounding lug,

as shown at right.

NOTE

Panel output wiring can be reconn­

ected to supply a dual voltage of

120/240 volts.. See Section 2. A 4-

wire cable is required.when supply­

ing dual voltage.

__________

VOLTAGE REGULATOR

The Voltage Regulator used on the TXP provides a constant voltage to

frequency ratio of 2 to 1, That is, when alternator frequency is 60 Hz,

voltage output will be 120 volts a-c ( + 27o). If frequency should drop

to 55 Hz, output voltage would also drop, to about 110 volts a-c.

The Voltage Regulator Assembly for

the Model 6931-1 TXP is shown at

right. Be sure to check the wiring

diagram for the specific model in­

volved. The following CHART lists

Regulator wires and their function.

Wire #

------T3---------

Connector

Pin

Function

1

#1

DC Current from (-) brush and slip ring

2

#2

AC Current from excitation windings

4

#4

DC Current to (+) brush and slip ring

6

#6

. . AC.Current from excitation windings

11

,#3

120 volt sensing from Sensing Transformer

22

#5

120 volt sensing from sensing Transformer

Issued 3-78

5.1