TEST 38 -

MAIN CIRCUIT BREAKER

NOTE

If the alternator has. been re.eonnected to provide a dual voltage

of 120 and 240 volts, the Main Circuit Breaker will be disconnec­

ted from the circuit. See WIRING DIAGRAMS, Section 2.

A.) Disconnect wires from Main

Circuit Breaker terminals ”A" and

”B", to prevent interaction. Set

VOM to "-)-DC" and to "Rxl" scale.

Zero the meter. Connect one meter

test probe to Terminal ”A" and

one probe to Terminal . ”B’.', With

the Circuit Breaker ON, meter

needle should swing upscale and

indicate ZERO ohms. With Breaker

OFF, meter needle, should drop all

the way downscale to !.'Infinity”,

TEST 39 -

ROTOR

A.) Use a ^ inch nut driver to re­

move the No. 8-32 screw that reta­

ins the Brush Inspection Cover to

the Rear Bearing Carrier. Remove

the Brush Inspection Cover, Set a

VOM to "Rxl" scale and to "+DC".

Zero the meter. Connect one meter

test probe to the brush terminal

furthest from the Brush Inspection

Cover opening. Connect the . s.e-cond

test probe to Ground, Meter needle

should swing upscale and indicate

approximately 13 Ohms. (+10 %). •

■ RESULTS: 1.) Tests Good...,,..............................

2.) Tests Bad,

.Continue tests in "Diagnostic

Flow Charts", Section 3

.Go to Paragraph "B"

B.) Use a

\

inch nut. driver to re­

move the Brush terminal screws, as

well as the Brush Holder reta.Lning

screws. With VOM set to. "+DG" and

to "Rxl" scale, repeat the test of

Paragraph "A" directl.y on the Rotor

Slip Rings, Meter needle should, swing

upscale and indicate, approximately 13

Ohms (+ 10%).

Issued 6-78

4.21