TEST 38 -
MAIN CIRCUIT BREAKER
NOTE
If the alternator has. been re.eonnected to provide a dual voltage
of 120 and 240 volts, the Main Circuit Breaker will be disconnec
ted from the circuit. See WIRING DIAGRAMS, Section 2.
A.) Disconnect wires from Main
Circuit Breaker terminals ”A" and
”B", to prevent interaction. Set
VOM to "-)-DC" and to "Rxl" scale.
Zero the meter. Connect one meter
test probe to Terminal ”A" and
one probe to Terminal . ”B’.', With
the Circuit Breaker ON, meter
needle should swing upscale and
indicate ZERO ohms. With Breaker
OFF, meter needle, should drop all
the way downscale to !.'Infinity”,
TEST 39 -
ROTOR
A.) Use a ^ inch nut driver to re
move the No. 8-32 screw that reta
ins the Brush Inspection Cover to
the Rear Bearing Carrier. Remove
the Brush Inspection Cover, Set a
VOM to "Rxl" scale and to "+DC".
Zero the meter. Connect one meter
test probe to the brush terminal
furthest from the Brush Inspection
Cover opening. Connect the . s.e-cond
test probe to Ground, Meter needle
should swing upscale and indicate
approximately 13 Ohms. (+10 %). •
■ RESULTS: 1.) Tests Good...,,..............................
2.) Tests Bad,
.Continue tests in "Diagnostic
Flow Charts", Section 3
.Go to Paragraph "B"
B.) Use a
\
inch nut. driver to re
move the Brush terminal screws, as
well as the Brush Holder reta.Lning
screws. With VOM set to. "+DG" and
to "Rxl" scale, repeat the test of
Paragraph "A" directl.y on the Rotor
Slip Rings, Meter needle should, swing
upscale and indicate, approximately 13
Ohms (+ 10%).