Factory Equipped Customer Wiring Connections
120VoitsOniy
PROCEDURE
1.
Disconnect wires No. 11 and No. 33 at
main circuit breaker,
2.
Disconnect wire No. Ti at main cir
cuit breaker and discard.
3.
Route wires No. 11 and 33 (discon
nected from main circuit breaker) to
customer connection panel.
4.
Connect customer wiring as shown
to obtain both 120 and 240 volts A-C.
XR
Main
Circuit
Breaker
Main Circuit Breaker is Not Connected
Grounding Lug
TXP RECONNECTED FOR 120/240 VOLT OUTPUT
Issued 3-78