A.

.) Remove Control Panel top cover.

Locate the white connector plug at

the rear of the panel. Unplug the

connector from its receptacle. Set

VOM to '’+DC” and to ”Rxl" scale,

then zero the meter. Connect one

meter test probe to receptacle pin

#2. Connect the second test probe

to receptacle pin #

6

. Meter needle

should swing upscale and indicate

about 1.8 to 2.5.ohms. This is the

resistance of the stator excitation

winding..

RESULTS: 1.), Windings check Bad. .................................................................... Replace Stator

2.) Windings check Good..................................................................Continue tests in

''Diagnostic Flow Charts", Section 3

B. ) Set the. meter swLtches ..to "+DC!' and to "Rxl0,000" scale. Zero the

meter. Connect one teat, probe to white receptacle pin #2, and the other

test probe to ground. Meter needle should not move.

RESULTS: 1.) Meter needle swings upscale.................................................Replace stator

2.) Meter needle does not move.................................................. Continue tests in

"Diagnostic Flow Charts", Section 3

TEST

35

-

C A R B O N B U I L D U P

A.) Excessive carbo.n buildup in the engine combustion chamber can ser­

iously affect engine power. Carbon deposits should be removed every

500 hours of operation, or whenever the cylinder heads are removed. If

engines are run at a steady load, it may be necessary to remove carbon

more often. Refer to ENGINE REPAIR section of this Manual for cylinder

head removal and installation procedures. When reinstalling cylinder

heads, bolts must be installed in the proper location on the head and

the cylinder head must.be properly torqued.

TEST 36 -

O U T P U T V O L T A G E

A,.) Use an accurate voltmeter or

the Model 5515 Load Bank to check

output voltage. When using a volt­

meter, connect one meter test

probe to alternator output lead T1

and the remaining test probe to

2

output leads T2. Voltage should he.

approximatel.y 125 volts at "no-load",

and.115 - 125 volts AC under load.If

voltage checks good, check frequency.

TEST 34 -

EXCITATION WINDINGS

Issued 6-78

4.19