RESULTS; 1.) Tests Good......................................Reconnect Wire #55, retain with

wire nut. Go to Test 45

2.) Tests Bad........................................Replace Diode Dl

TEST 45

- S T A T O R B A T T E R Y C H A R G E W I N D I N G S

A.) Remove the 15 Amp Fuse. Discon­

nect Wire #77 from Battery Charge

Circuit Breaker, Remove wire nut

from the Wire #55 connection, near

Diode Dl, then disconnect the wires.

Set VOM to ”+DC” and to "Rxl” scale.

Zero the meter. Connect one meter

test probe to Wire #55, Connect the

other test probe to Wire #77, Meter

needle should swing upscale and in­

dicate approximately 0,20 Ohms.

Wire No. 77

Battery

Charge Circuj^

Breaker

^ Nut

Wire

No 55

Wire No. 78

RESULTS

1, ) Tests Good,

2. ) Tests Bad..

.Go to Paragraph ’’B”

.Replace Stator

B.) With 15 Amp Fuse still removed, set VOM to "+DC" and to *'RxlO,000"

scale. Zero the meter. Connect one meter test probe to Wire #55, and

the other test probe to Ground, Meter needle should not move (infinity),

RESULTS; 1,) Meter needle moved upscale.............................................. Shorted condition indi­

cated, replace Stator

2,) Meter needle did not move,,,........................................ .Checks Good

Issued 6-78