TEST 13 -

IGNITION STATOR

A.) Remove the wire nut from Wire

No. 20.at the Low Oil Switch. Dis­

connect the wire, to prevent inter­

action. Then proceed a.s. follows:

^

a. Set VOM to ”Rxl00" and to ”+DC”.

Zero the meter. Connect one meter

^ A test probe to Pin No. 2 of the Ig-

cJwoj/nition Module receptacle. Connect

the second test probe to ground.

^v> Meter needle, should swing upscale

R^-^j^nd read appro.ximately 225 Ohms

(+10'^°)* This is the Ignition State

Charge Coil resistance.

RESULTS: 1.) Tests Bad....................................... .

2.) Tests Good....................... ...........

b. S'et the VOM to ”+DC" and to ’’Rxl”

scale. Again zero the meter. Connect

one meter test probe to Ignition

Module receptacle Pin No. 3, and the

second probe to ground. Meter needle

should

swing

upscale

and,read

approx

imately

6

Ohms. This is the Ignition

Stator Trigger Coil resistance.

Reconnect Wire No. 20 at the

fore proceeding to next test

TEST 14 -

IGNITION COIL

VOM

,Install new Ignition Stator

.Continue tests in "Diagnostic

Flow Chart", section 3

Low Oil Switch and retain with wire nut be-

, Also install Ignition Module,.

A.)

n

Set

M T

to "Rxl" scale and to

’+DC", then zero the meter. Conn­

ect one meter test probe to Pin 4

of

the

Ignition

Module

receptacle.

Connect

the

remaining

test

probe

to Ignition Module receptacle Pin

1.

Meter needle should swing up­

scale

and

indicate

the

Ignition

Coil

primary

winding

resistance

(about 0.5 Ohms).

4.8

Issued 3-78