RESULTS: 1.) Starter Pinion Gear does
not move outward..............................
2.) Pinion Gear does move out
ward.’...................................................
Inspect helix on clutch for
freedom of operation. If
sticking due to dirt, clean
entire starter drive. If
any parts are damaged or
worn, replace.
.Continue tests in ’’Diagnos
tic Flow Charts", Section 3
TEST 7 -
STARTER RING GEAR
A.) Inspect Starter Ring Gear for
damaged teeth.
RESULT: 1.^ Ring. Gear damaged,
2.) Ring Gear Good....
.Replace
.Continue tests in "Diagnostic
Flow Chart", Section 3
TEST
8
-CHECK SPARK
A.) Remove lead from one spark plug.
Connect the lead to Spark Plug test-
Part No. 41503. Attach the spark
er,
plug tester clamp to a clean, paint-
free ground. Crank the engine - a
sharp, "snappy" spark should be seen.
Repeat the test for the remaining
spark plug.
_______________________
^CAUTION
NEVER crank the engine, with a spark
plug or spark plug lead removed, un
less the spark plug or.lead Is conn
ected to a clean ground. Failure to
ground the plug or lead can damag.e.
the ignition coil. _______________________________
RESULT: 1,)A sharp, snappy spark is NOT
observed......................................................
2.)A sharp, snappy spark is ob
served. ....................................... ................
Issued 3-78
.Continue tests in "Diagnostic
Flow Charts", Section 3
.Continue tests in "Diagnostic
Flow Charts", Section 3
4^5