Generac Power Systems TXP User Manual
Page 49
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
VOLTAGE REGULATOR ADJUSTMENT
The Voltage Regulator is adjusted at the factory and normally requires
no additional adjustment. If the engine is running at 62 Hz "No-Load"
and voltage readings are incorrect, the Regulator may be adjusted. An
accurate Frequency Meter and Voltmeter are required to adjust the Reg
ulator. The Model 5515 Load Bank.provides both these instruments. The
following procedure covers use of the Load Bank for Regulator adjust
ment.
1. Connect 3-wire cord set (Part
No. 27821) to alternator output
wires as shown above. Plug the
connector plug into the 120 volt,
3-prong connector plug on the
Load Bank. Set ALL Load Bank Hea
ter element switches to OFF. Set
Ammeter Hi-Lo Range Selector
Switch to 0-50 AMPS. MAKE SURE
THE LOAD BANK HEATER ELEMENT COV
ER IS OPEN.
2. Adjust carburetor jets and go
verned idle as outlined in Test
23, Page 4.14,
3. Adjust Governor as outlined in
Test 32, Page 4.18 and 4.19.
5.2
Issued 3-78