TEST 3

-START - STOP SWITCH

Remove the 15 amp Fuse to disconn­

ect the starting circuit. Then re­

move

2

screws that retain the top

panel. Finally, remove the top

panel.

/^5

RESULTS: 1.) Switch tests Bad..

2.) Switch tests Good.

Set the switches of a Volt-Ohm-

Milliammeter to

and to ''Rxl"

scale. Connect meter test probes

together and ”Zero" the meter.

Connect the meter test.probes to

the switch center and lower termi­

nals, as shown above. Meter needle

should not move. Hold Switch at

STA.RT position - meter needle

should, move upscale, to "zero”.

Hold switch at STOP - meter needle

should drop all the way downscale

to "Infinity”.

.......................Install a new switch

...................... Continue tests

Connect the VOM test probes to the

Switch terminals as shown at right.

Hold Start./Stop Switch at START -

meter needle should not move.

Release the Switch to NEUTRAL po­

sition - the meter needle, should

not move.

Hold the Switch at STOP - the. meter

needle should swing upscale and. ind'

icate "zero" ohms.

RESULTS: 1.) Switch tests Bad..

2.) Switch tests Good.

.Install a new Sta.rt/Stop Switch

.Reconnect wires to Switch

Install top panel

Install 15 Amp Fuse

Continue Tests

4.2