Issued 3-78 – Generac Power Systems TXP User Manual

Page 28

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

CAUTION

Before installing Low Oil Switch Cover, make sure the float arm is

riding on top of the switch actuating lever. If float arm has dropped

off of switch actuating lever, engine will not shut down when oil

level in tank is low.

RESULTS:.!.) Switch tests Bad............................................................ Replace Switch

2.) Switch tests.Good...............Continue tests in "Diag­

nostic Flow Charts", Sec­

tion 3

TEST

11

-SPARK PLUG

A,) Remove one spark plug. Connect

spark plug wire to plug. Ground

spark plug against engine. Hold

Start/Stop Switch at START and ob­

serve spark plug. A sharp, snappy

spark should be seen. Repeat test

for second spark plug.

CAUTION

NEVER crank engine with a spark

plug or spark plug wire removed,

unless the spark plug or wire is

connected to a clean ground.

Failure to ground the plug or

lead can damage the Ignition coil,

RESULTS: 1.) Sharp, snappy spark is

NOT observed.............. ........................ ................ .Replace spark plug

2.) Sharp, snappy spark IS

observed,....... ................................................................ .. .Continue tests in

"Diagnostic* Flow

Charts", Section 3

Test

12

-

IGNITION MODULE

A.) Unplug the Ignition Module

from its receptacle. Inspect the

connector pins in the module and

module receptacle - make sure

the pins are not bent or pushed

in. Install a new (or "shop") ig­

nition module and check for norm­

al spark.

RESULTS: 1.) Normal "hot" sparking...................................................Install a new Ignition

Module, continue tests

2.) Normal sparking NOT observed.... Continue tests in"Diagnos-

tic Flow Charts", Section 3

Issued 3-78