•C.) Disconnect Wire #14 at Fuel Pump
terminal. Set VOM to ”+DC” and to 50
Volt scale. Connect the POSITIVE (+)
meter test probe to the terminal end
of Wire #14. Connect the COMMON test
probe to ground. Crank the engine -
meter
needle
should
deflect
upscale
and
indicate
battery
voltage
(about
12 volts DC).
RESULTS: 1.) Meter does NOT read 12 volts............................................*...Go to Paragraph ”D’
2.) Meter indicates 12 volts, but pump
does not pulse when Wire #14 is
connected to its terminal.'......................................................Replace Fuel Pump
D,) Check Wire #14, between the Fuel
Pump and terminal strip in control
panel, for open or shorted condition.
RESULTS: 1.) Wire #14 checks Good................................................... Continue tests in”Diagnos-
tic Flow Charts", Section 3
2.) Wire #14 checks Bad..................................................Repair/Replace Wire #14
TEST 22
-CHECK INSTALLATION
Does the installation include a second in-line fuel filter? If so,, check
the filter for clogging. If a shutoff valve is installed in the fuel
supply line, make sure the valve is open. Finally, make sure the air in
let opening in the door is large enough. An insufficient supply of cool
ing air will result in high compartment temperatures and possible fuel
line vapor lock. Refer to INSTALLATION MANUAL, RECREATIONAL VEHICLE ALT
ERNATORS (Part No. 49204).
Issued 3-78
4.13