•C.) Disconnect Wire #14 at Fuel Pump

terminal. Set VOM to ”+DC” and to 50

Volt scale. Connect the POSITIVE (+)

meter test probe to the terminal end

of Wire #14. Connect the COMMON test

probe to ground. Crank the engine -

meter

needle

should

deflect

upscale

and

indicate

battery

voltage

(about

12 volts DC).

RESULTS: 1.) Meter does NOT read 12 volts............................................*...Go to Paragraph ”D’

2.) Meter indicates 12 volts, but pump

does not pulse when Wire #14 is

connected to its terminal.'......................................................Replace Fuel Pump

D,) Check Wire #14, between the Fuel

Pump and terminal strip in control

panel, for open or shorted condition.

RESULTS: 1.) Wire #14 checks Good................................................... Continue tests in”Diagnos-

tic Flow Charts", Section 3

2.) Wire #14 checks Bad..................................................Repair/Replace Wire #14

TEST 22

-CHECK INSTALLATION

Does the installation include a second in-line fuel filter? If so,, check

the filter for clogging. If a shutoff valve is installed in the fuel

supply line, make sure the valve is open. Finally, make sure the air in­

let opening in the door is large enough. An insufficient supply of cool­

ing air will result in high compartment temperatures and possible fuel

line vapor lock. Refer to INSTALLATION MANUAL, RECREATIONAL VEHICLE ALT­

ERNATORS (Part No. 49204).

Issued 3-78