TEST 16

-NO FUEL FLOW

At carburetor inlet, spread clamp

and slide it down the fuel inlet

hose. Disconnect the hose from in­

let fitting - BE CAREFUL NOT TO

BREAK THE FITTING. Hold open end

of fuel hose over a suitable con­

tainer. Hold Start/Stop Switch,at

START to crank engine. Check for

fuel flow from fuel inlet hose.

A’

DANGER

Gasoline vapors are highly flammable and. explosive. Do not Jbermit

smoking, open flame or sparks in the vicinity while checking for

fuel flow.

RESULTS: 1.) Fuel.. Flow Bad.............................................Continue tests in "Diagnostic

Flow Charts", Section 3

2.) Fuel Flow Good........................................Continue tests in "Diagnostic

Flow Charts", Section 3

TEST 1 7 - 4 AMP FUSE

A.) Remove 15 Amp fuse to disconn­

ect starting, circuit. Remove the

2

screws that retain the top panel.

Remove the top panel.

B.) Remove the 4 Amp Fuse from the

Printed Circuit Board. Check visu­

ally for an open fuse element. Set

VOM to "+DC" and to "Rxl" scale.

Zero the meter. Connect meter test

probes to both ends of fuse. Meter

needle should swing upscale and in­

dicate "zero".

RESULTS:

1

.) Fuse checks Good................................... Continue tests in

Diagnostic Flow Charts"

Section 3

2.) Fuse checks Bad..................................Replace Fuse

4.10

Issued 3-78