12-8

Display

(Function mode 1)

(Function mode 2)

Setting, change

sequence

Function

Function

Initialization display

Initialization

contents

Setting contents

No.

name

contents

13

F-20

DC braking

DCB SW

OFF

OFF

ON/OFF

• DC braking

DC

selection

ON: DC braking available

injection

OFF: DC braking unavailable

braking

DC braking

DCB KIND

LVL

LVL

LVL/EDG

• DC braking method selection

type

LVL: Level operation

selection

EDG: Edge operation

DC braking

DCB F

0000.5 Hz

0.5 Hz

0 to 400.0 Hz

• The frequency at which the

frequency

DC braking starts is set.

selection
DC braking

DCB V-STA

00

0

0 to 20

• The DC braking force at start

force selec-

is set.

tion (at start)
DC braking

DCB V-STP

00

0

0 to 20

• The DC braking force at stop

force selec-

is set.

tion (at stop)
DC braking

DCB T-STA

000.0 s

0 s

0 to 600.0

• The DC braking time at start

time selec-

is set.

tion (at start)
DC braking

DCB T-STP

000.0 s

0 s

0 to 600.0

• The DC braking time at stop

time selec-

is set.

tion (at stop)
DC braking

DCB STOP-T

0.00 s

0 s

0 to 5.00

The output frequency is

output cut-

lowered to the DC braking

off time

frequency and the free run

adjustment

time during execution of DC

braking is set.

14

F-21

Dynamic

BRD-%ED

001.5%

1.5%

0 to 100.0

• The allowable usage ratio of

braking

the braking resistor for 100

setting

seconds is set. (NOTE 1)

15

F-22

Allowable

IPS TIME

1.0 s

1.0 s

0.3 to 25 s

• When an instantaneous power

The

instantaneous

failure occurs, the allowable

allowable

power failure

time until the power failure is

usage

time setting

recovered is set.

ratio of

Reclosing

IPS WAIT

001.0 s

1.0 s

0.3 to 100.0 s

• The waiting time until the

the

standby after

rerunning starts after an

braking

instantaneous

instantaneous power failure

resistor

power failure

occurs and is recovered is set.

for 100

recovered

seconds

Instantaneous

IPS POWR

ALM

ALM

ALM/FTP/

ALM: Alarm output

is set.

power failure

RST/ZST

ZST: 0 Hz start retry

restart

FTP: Retry after frequency

selection

matching is stopped

RST: Rerunning start retry

Trip selection

IPS TRIP

OFF

OFF

ON/OFF

When an instantaneous power

during stop

failure occurs:

at under

ON: Trip

voltage

OFF: Non-trip

16

F-23

Electronic

E-THM CHAR

SUB

SUB

CRT/SUB/FRE

• Electronic thermal characteris-

Electronic thermal

tic setting CRT: Constant

thermal

characteristic

torque characteristic

selection

SUB: Reduced torque charac-
teristic
FRE: Free characteristic

Electronic

E-THM LEVEL

100%

100%

20 to 120%

thermal level
setting

NOTE 1: Initial setting of usage ratio

1.5%

055-075L/HF

0%

110-550L/HF