beautypg.com

Hitachi J300U Series User Manual

Page 58

background image

7-18

Contents and display

Extension

function

code

1

2

FUNC

FUNC

.

.

Carrier
frequency
setting

Set the switching frequency of the power module.

Initial value

(NOTE 1)

NOTE 1: The initial value of carrier frequency

varies with the inverter capacity.
When VP1 to VP3 is selected,carrier
frequency is automatically changed to
VT.

Carrier frequency initial value

1

2

FUNC

.

Multispeed
setting 1

Multispeed
setting 2

Multispeed
setting 3

Set the output frequency of each multispeed speed. When setting four or more speeds, refer to the
item of output frequency setting.

Initial value

FUNC

FM

CM1 PLC

P24

(8)

REV

FW

(7)

CF1

(6)

CF2

(7) CF1

(6) CF2

ON

OFF

OFF

ON

ON

ON

(400)

In the case
of multispeed
setting 1

In the case of multispeed setting 2

In the case of multispeed setting 3

Example of the connection method
Refer to Page 5-5

Multispeed

Control circuit

terminal

Multispeed 1

Multispeed 2

Multispeed 3

initial value

16 kHz

model type

055 to 150 L/HF

220 L/HF

300 to 370 L/HF

450 to 550 L/HF

12 kHz

10 kHz

6 kHz

1

2

FUNC

FUNC

Frequency
command
sampling
frequency
setting

Set the frequency commands (voltage frequency command (O-L terminal signal), current frequency
command (OI-L terminal signal), and the number of samplings.

Initial value

NOTE: How to set

The number of samplings is set to 1.
The reaction time becomes shorter, but
the output frequency becomes likely to
vary.

The number of samplings is set to 8.
The reaction time becomes longer, but
the output frequency becomes stable.

:

:

¥
¥
¥
¥

Example of Multispeed setting

NOTE: When using four or more multispeed commands,

use the multispeed terminal (CF3) as an input terminal.

8 kHz

6 kHz

5 kHz

3 kHz

CT

VT

750 to 1100HF

3 kHz

2 kHz

1320 to 2200HF

2 kHz

2 kHz