Hitachi J300U Series User Manual

Page 101

background image

12-10

Display

(Function mode 1)

(Function mode 2)

Setting, change

sequence

Function

Function

Initialization display

Initialization

contents

Setting contents

No.

name

contents

19

F-26

Frequency

LIMIT L

0000.0 Hz

0 Hz

0 to 120.0

The lower limit of the frequency

Frequency lower limiter

(400) Hz

to be set is set. When the lower

limiter

setting

limit is 0, the setting is invalid.

Frequency

LIMIT H

0000.0 Hz

0 Hz

0 to 120.0

The upper limit of the frequency

upper

(400) Hz

to be set is set. When the upper

limiter

limit is 0, the setting is invalid.

setting

20

F-27

Jump

JUMP F1

0000.0 Hz

0 Hz

0 to 400 Hz

• The section where frequencies

Jump

frequency

are to be jumped is set.

frequency setting (1)

• Up to three locations can be

set.

• When the number of locations

is 0, the setting is invalid.

Jump

JUMP F2

0000.0 Hz

0 Hz

0 to 400 Hz

frequency
setting (2)
Jump

JUMP F3

0000.0 Hz

0 Hz

0 to 400 Hz

frequency
setting (3)
Jump

JUMP W

0.5 Hz

0.5 Hz

0 to 9.9 Hz

• The frequency width where

frequency

frequencies are jumped is set.

width setting

21

F-28

STOP key

STOP-SW

ON

ON

ON: STOP key

Whether or not to make the

validity

valid

STOP key valid during terminal

selection

OFF: STOP key

running is selected. In the

during

invalid

Remote mode, the STOP key is

terminal

always valid.

running

22

F-29

Running

F/R SW

FRE

FRE

FWD/REV/

FWD: Only forward run

direction

FRE

REV: Only reverse run

selection

FRE: Both forward run and
reverse run valid

Reverse run

F/R PREV

OFF

OFF

ON/OFF

Reverse run prevention

prevention

ON:

selection

OFF:

Reduced

F/R RVS

6

6

0 to 6

voltage
soft start
setting

23

F-30

Maximum

F-MAX-L

120 Hz

120 Hz

120/400 Hz

Maximum frequency switching:

frequency

120: 120 Hz 400: 400 Hz

selection

24

F-31

Analog input IN ANA

10 V

10 V

10/5

Input voltage maximum level

External

voltage

10: Max. 10 V 5: Max. 5 V

analog

selection

frequency External

IN EXS

0000.0 Hz

0 Hz

0 to 120.0 (400)

• Frequency at which the

command

frequency

external input starts

start setting
External

IN EXE

0000.0 Hz

0 Hz

0 to 120.0 (400)

• Frequency at which the

frequency

external input is maximized

end setting
External

IN EX%S

000%

0%

0 to 100

• Input start level

frequency
start setting
rate
External fre- IN EX%E

100%

100%

0 to 100

• Input maximum level

quency end
setting rate
External

IN LEVEL

0 Hz

0 Hz

0 Hz/ExS

EXS: Start at EX%S setting

command

rate or less

start point
selection