7-30

Contents and display

Extension

function

code

Output
terminal
setting
11 and 12

A terminal function is allocated to each of the output intelligent terminals 11 and 12. When using
a function other than the standard set functions or changing the terminal order, set the function for
each terminal.

1

2

FUNC

Code

Function name

Terminal

rating plate

Initial
setting

Output terminal setting 11

C10

C11

Output terminal setting 12

11

0

12

1

Arrary of codes and intelligent terminals

PCB terminal array

The setting method is the same
as that of the input terminals

to .

Setting method

Press the key once for the terminal code to be set.

The set values of the terminals which are set at present are displayed. Display the set value
of the terminal to be used from the function list indicated below by pressing the key

and and then press the key.

The display is returned to the code display and the terminal function is changed.

FUNC

1

2

FUNC

FUNC

Enter the set value of the terminal name
to be used by pressing the keys and .

Set value

Function name

0

1
2

Input terminal function list

FA1

RUN

OTQ

Frequency arrival signal

Signal during running

Overtorque signal (Note)

Abbrevia-

tion

Precautions for terminal setting

Same terminals cannot be set between and .
When moving a terminal name to another terminal, set another terminal which is not to be
ued at the setting source before inputting the set value to the setting destination and then
select the terminal name which is to be set at the setting destination.

CM2

12
11

AL2

AL1

AL0

NOTE: The torque of the overtorque signal can be set by the remote operator. The initial

values of motoring and regeneration are 100% torque. The overtorque signal can be

used only under the sensorless vector control.