A-29 – Hitachi J300U Series User Manual

Page 141

background image

A-29

Display with HOP, HRW Display with DOP, DRW

Function No. with digital operator

Data read/copy

Function mode

Layer

Data display

No.

Data display

Alterability

No.

Data

HRW DRW

Electronic thermal characteristics

3-5-1

6 F2

0 Hz

F-23

E-THM F2 0000 Hz

N

Y

N

free setting (frequency 2)

Electronic thermal characteristics

7 A3

24.0 A

E-THM A3 24.0 A

N

Y

N

free setting (current value 3)

Electronic thermal characteristics

8 F3

73 Hz

E-THM F3 0073 Hz

N

Y

N

free setting (frequency 3)

Overload limit level setting

3-5-2

1 LEVEL 125%

F-24

OLOAD LEVEL 125%

N

Y

Y

Overload limit constant setting

2 CONST 1.0

OLOAD CONST 01.0

N

Y

Y

Overload limit selection during

3 ACC

1: ON

OLOAD ACC ON

N

Y

Y

acceleration

Frequency lower limiter setting

3-5-3

1 LIML

0.0 Hz

F-26

LIMIT L 0000.0 Hz

Y

A5

0.0

Y

Y

Frequency upper limiter setting

2 LIMH

0.0 Hz

LIMIT H 0000.0 Hz

Y

A6

0.0

Y

Y

Jump frequency (1)

3 F1

0.0 Hz

F-27

JUMP F1 0000.0 Hz

Y

A7

0.0

Y

Y

Jump frequency (2)

4 F2

0.0 Hz

JUMP F2 0000.0 Hz

Y

A8

0.0

Y

Y

Jump frequency (3)

5 F3

0.0 Hz

JUMP F3 0000.0 Hz

Y

A9

0.0

Y

Y

Jump frequency width setting

6 WIDTH 0.5 Hz

JUMP W 0.5Hz

N

Y

Y

Allowable instantaneous time

3-5-4

1 TIME

1.0 s

F-22

IPS TIME 1.0 s

N

Y

Y

Reclosing stand-by after instantaneous

2 WAIT

1.0 s

IPS WAIT 001.0 s

N

Y

Y

power failure recovered

Instantaneous power failure restart

3 POWR

0: ALM

IPS POWR ALM

Y

A34

0

Y

Y

selection

Trip selection during stop at under

4 TRIP

1: OFF

IPS TRIP OFF

N

Y

Y

voltage

Max. frequency selection

3-5-5

1 MAXF

0: 120 Hz F-30

F-MAX-L 120 Hz

Y

A64

120

Y

Y

Software lock selection

2 SLOCK 1: MD1

F-25

S-LOCK MD1

N

Y

Y

STOP key validity selection

3 STOP

1: ON

F-28

STOP-SW ON

N

Y

Y

Running direction selection

4 F/R

2: FRE

F-29

F/R SW FRE

N

Y

Y

Reverse run prevention

5 PREV

0: OFF

F/R PREV OFF

N

Y

Y

Reduced voltage soft start setting

6 RVS

6

F/R RVS 6

Y

A58

6

Y

N

Analog input voltage selection

3-6-1

1 V

1: 10

F-31

IN ANA 10V

Y

A48

1

Y

Y

External frequency start setting

2 EXS

0.0 Hz

IN EXS 0000.0 Hz

Y

A26

0.0

Y

Y

External frequency end setting

3 EXE

0.0 Hz

IN EXE 0000.0 Hz

Y

A27

0.0

Y

N

External frequency start rate setting

4 EX%s

0 %

IN EX%S 000 %

N

Y

N

External frequency end rate setting

5 EX%E

100 %

IN EX%E 100 %

N

Y

N

External frequency start point setting

6 LEVEL 0 Hz

IN LEVEL 0 Hz

N

Y

Y

Frequency command sampling

7 F-SAMP 8

IN F-SAMP 8

Y

A11

8

Y

N

frequency setting

Arrival signal output pattern selection

3-6-2

1 PTN

0: CST

F-32

ARV PTN CST

Y

A49

0

Y

Y

Arrival frequency setting for acceleration

2 ACC

0.0 Hz

ARV ACC 0.0 Hz

Y

A39

0

Y

Y

Arrival frequency setting for deceleration

3 DEC

0.0 Hz

ARV DEC 0.0 Hz

Y

A40

0

Y

Y

Overtorque signal rate for plus torque

4 V

100 %

F-33

0V-TRQ V 100 %

N

Y

N

Overtorque signal rate for minus torque

5 R

100 %

0V-TRQ R 100 %

N

Y

N

set
value