beautypg.com

Hitachi J300U Series User Manual

Page 62

background image

7-22

Contents and display

Extension

function

code

1

2

FUNC

FUNC

Monitor
signal
selection

Set value

Function

0

Analog output frequency monitor

1

Analog current monitor

2

Analog torque monitor (Note)

Initial value

Setting method

Select the output monitors signal at the control circuit terminal FM from
the table indicated below.

3

Digital output frequency monitor

Initial value

NOTE:

Use the analog torque monitor function only in the
sensorless state. Under the V/f control, an appropriate
value is outputted. The accuracy is ±20%
(a rough value).

1

2

FUNC

FUNC

Analog
input
selection

Set value

Function

0

Max. 5 V input

1

Max. 10 V input

Initial value

Setting method

Set the maximum voltage to be supplied between the terminals 0 and L.

Initial value

Input impedance

30 k

Terminal connection example

VR0

(500

to 2k

Ω)

DC0 TO 5V
DC0 TO 10V

+

Ð

H

O

01 L

H

O

01 L

Output monitor signal

Frequency monitor

Current monitor

Torque monitor

Maximum frequency

200% of the rated current

200% of the rated torque

Output full-scale value

Analog

1

2

FUNC

FUNC

Frequency
converted
value
setting

Initial value

Setting method

Set a converted value for frequency converted value monitoring. The product of this setting and the
ouptut frequency (d0) is displayed as the value for the frequency converted value monitor (d3).

1