A-18 – Hitachi J300U Series User Manual

Page 130

background image

A-18

Mg1

Mg2

THRY

IM

R(L1)
S(L2)
T(L3)

(T1)U
(T2)V

(T3)W

H
O
L
FW
RV
CS
CM1

AL1
AL2
AL0

ELBC

ELB

Mg

FWY

RVY

CSY

Mg

ON

Mg1

Mg2

CS

FWY

RVY

ON

ON

ON

ON

OFF

NOTE 1: When the ELB trips due to a ground-fault, the commercial power
source circuit will not operate. Therefore, when a backup is
necessary, take a commercial power source circuit from the ELBC.

NOTE 2: Use weak current relays for FWY, RVY, and CSY. Separate AC
relays from DC relays. The above sequence is a reference drawing
for timing.

Mg1 and Mg2 interlocking time

Set time by timer 2C

(The time is generally set to 1 to 3 seconds. Error may come when the set time is 4 seconds or more.)

[F-22] IPS WAIT

Inverter running
start

Running

20 ms or more

Connection example diagram and timing for commercial power source switching running