7-20

Contents and display

Extension

function

code

1

2

FUNC

FUNC

Instanta-
neous
restart
selection

Set value

Function

0

Alarm output after tripped

1

Deceleration stop at the time

of restart

2

Frequency matching start at the time

of restart ( Note 1)

Initial value

Setting method

Set the inverter retry method when a power error occurs.
Select the set value of the retry method to be used.

3

0 Hz start at the time of restart

NOTE 1:

NOTE 2:

When the base frequency is one of the following ones, frequency matching may restart at 0 Hz.
When the base frequency is 60 Hz: Driven at 40 Hz or less
When the base frequency is 50 Hz: Driven at 30 Hz or less
For other precautions, refer to Chapter 1, "Instantaneous stop restart" of Appendix 2.

Since the retry mode is selected, the equipment restarts for trips of overcurrent, overvoltage, or undervoltage.
For undervoltage, 16 retries (17th trip) are executed.
For overcurrent or overvoltage, 3 retries (fourth trip) are executed.
Do not use this function for a case that a fallen substance should be held by the machine brake when the motor
is in the free-run mode.

Initial value

Restart
selection

,,

,,

External
frequency
setting
start

External
Frequency
setting end

Set the frequency for starting output for an external frequency command (0 to 10 V, 0 to 5 V,
4 to 20 mA) and the frequency for ending output. When 0 Hz is set, this function will be canceled.

1

2

FUNC

Initial value

Setting method

FUNC

.

(400)

,

External frequency
setting start

External frequency
setting end

Same as A26

Output frequency (Hz)

Frequency
command

0

10 V

0

5 V

4

20 mA

NOTE 1:

NOTE 2:

NOTE 3:

NOTE 4:

The standard setting is 0 Hz.
In this case, the selected V/f
pattern is used for running.
When changing the V/f pattern
after A 26 (start) and A 27 (end)
are set, readjust A 26 (start) and
A 27 (end).
When A 26 (start) > A 27 (end)
is set and the frequency command
value is minimized (0 V or 4 mA),
the output frequency may be
lowered than the value which is
set by A 26 by 0.1 to 0.3 Hz.
The reason is that it is judged that
there is some frequency due to
noise on the signal line and it is a
normal operation.
The setting shown left is also
possible with F31 of the remote
operator.

60

30

50

,

Output
frequency
(Hz)

60

10 V
5V
20mA

0

8 V

0

4 V

4

16.8

2
1
7.2

Start setting
command (20%)

Frequency
command

End setting
command (80%)