5-13

Terminal symbol

Terminal name

Description

H

Frequency command power

• Initialization of a voltage signal by an external command

terminal

is between 0 and 10 VDC. (Switching from 0 to 5V is executed

by A48.) When inputting 4 - 20 mA, turn the input terminal at
ON.

O

Frequency command
terminal (voltage command)

OI

Frequency command
terminal (current command)

L

Frequency command
common terminal

CM2

Common terminal 2

Common terminal for intelligent output terminal

FA1

Frequency arrival signal

When each operator is used, and arrival signal can be
outputted at an optional frequency.

RUN

Signal during run

The transistor output is turned ON during running.
(Outputted even during DC injection braking)

OTQ

Over-torque signal

The transistor output is turned ON when the torque is more
than the set value.
The set value can be changed by the remote operator.
Use this function only under the sensor less vector control.

AL0

AL1

Fault alarm terminal

AL2

NOTE 1: To set four or more multispeeds, use the CF3 terminal.

NOTE 2: When an inconvernience occurs in the above characteristics, adjust it using

and

. The sum of both analog input signals is outputted

When selecting one of analog input current and voltage, make sure that the other
is not inputted.

11 • 12

H O OI L

VRO

(500

to 2 k

)

DC0 to 10 V

DC0 to 5V

Input impedance 30 k

+

-

+

-

H O OI L

H O OI L

DC4 to 20 mV

Input impedance 250 k

When a current is inputted from between OI and L and the value is 4 mA,
the output frequency may 0.6 Hz. If this occurs, set a value more than the
frequency which is outputted by [A 4] start frequency setting.

(NOTE 2)

AL2 AL1 AL0

Normal: AL0-AL1 close
Abnormal, Power off:
AL0-AL1 open

Contact rating
250 VAC

30 VDC

2.5 A (Resistor load)
0.2 A (Cosø=0.4)
3.0 A (Resistor load)
0.7 A (cosø=0.4)

Min 100Vac
10 mA
5 VDC
100 mA