7-17

Contents and display

Extension

function

code

1

FUNC

.

Frequency
upper,
lower
limiter

,,

,,

➤ Settable range

2

FUNC

Initial value

(400)

Maximum
frequency limiter

1

FUNC

.

2

FUNC

Initial value

(400)

Minimum
frequency limiter

Setting example
(When an upper limit of 45 Hz and a lower
limit of 20 Hz are set)

Output frequency
(60 Hz)

Upper limiter

Lower limiter

45

20

0

Frequency command

(F-SET)

NOTE: Setting conditions

0 Hz or upper limit

lower limit

When 0 Hz is set, the limiters will not operate.

Set the limits of frequency setting within the start frequency adjustment range and
maximum frequency setting range. When a value beyond the limits is inputted from the operator,
it will not be stored. Even if a value beyond the limits is inputted as external analog input, the set
value will not be changed.

➤ ➤

➤ ➤

1

FUNC

.

2

FUNC

Initial value

In the case
of jump frequency 1

Jump
frequency
setting 1

To avoid a resonance with the load, the frequencies at up to 3 points can be jumped. The setting
order and the execution order may be changed.

The frequency equivalent to the jump frequency setting width (± 0.5 Hz) (Note 1) cannot be set as
a jump frequency.

f

f

0

0

Set frequency (V)

Output frequency (V)

f

45

30

10

0

Speed command

frequency

In the case
of jump frequency 2

In the case
of jump frequency 3

Jump
frequency
setting 2

Jump
frequency
setting 3

NOTE 2 : As to the frequencies which are set by the jump frequency setting function, the set

frequencies are jumped but the output frequencies pass.

Setting example

Jump frequency 1: 10 Hz
Jump frequency 2: 30 Hz
Jump frequency 3: 45 Hz
Jump frequency width: 0.5 Hz

Output

frequency

Adjustment range

(V)

Deceleration

Acceleration

Frequency which
jumps by 1.0 Hz

0.5 Hz

0.5 Hz

NOTE 1 : The jump frequency can be set by the remote operator.