WARNING

l

If the retry mode is selected, do not approach the inverter unnecessarily. It will be
restarted suddenly after it trips/stops. (Design the inverter so that the safety can be assured
even in such a restart.) Otherwise, bodily injury will result.

NOTE: Since the retry mode is selected, the equipment restarts for trips of overcurrent,

overvoltage, or undervoltage. For undervoltage, 16 retries (17th trip) are
executed. For overcurrent or overvoltage, 3 retries (fourth trip) are executed.

Do not use this function for a case that a fallen substance should be held by the
machine brake when the motor is in the free-run mode.

In the following cases, the equipment may start at the lowest frequency (called 0 start).

1)

When the reclosing standby time (function mode F-22, IPS WAIT) after the
instantaneous power failure is recovered is set to 3 seconds or more

2)

When the output frequency is more than 60 Hz

3)

When the base frequency is 60 Hz: Driven at 30 Hz or less

When the base frequency is 50 Hz: Driven at 25 Hz or less

4)

When the induced voltage of the motor attenuates earlier (for example, a pump or high-
speed gear which causes the motor to decelerate for several seconds or less)

NOTE: The inverter control power holding time may be slightly different depending on

the inverter rating, the load status, remote operator (copy unit) connection status,
and input voltage.

t

0

t

0

t

0

t

1

t

1

t

1

t

2

t

2

t

2

Power supply

Inverter control

power supply

Allowable

instantaneous

power failure time

F-22

(data set value)

Inverter output

F-22 (IPS WAIT set value)

About 1 second

An instantaneous power failure trip

(Inst.p-f) occurs because

t

2>

t

0.

t

1: Control power holding time

when power is turned OFF

The operation restarts because

t

2>=

t

0.

t

2: F-22 (IPS TIME set value)

The running restarts when a running

command is issued because

t

2>

t

1.

t

0: Instantaneous power failure time

Alarm