Page 145

background image

A-33

3.

Data Setting Method

(1)

Digital operator

Refer to

9 0

A

9 1

A

9 2

A

9 4

A

9 5

A

9 6

A

of the extended funciton

mode contents (pages 7-26 and 7-27).

(2)

Remote operator

Setting item

Setting range

PID IN-SEL IN

The PID LVL set value is assumed as the target value.

OUT

The target value depends on the frequency setting method.

PID LVL

0 to 200%

PID P

0 to 5.0

PID I

0 to 15.0

PID D

0 to 100.0

PID MODE

MD0

Built-in PID control OFF

MD1

An analog current input is used as the feed-back signal.

MD2

An analog voltage input is used as the feed-back signal.

MD3

An analog current input is used as the feed-back signal.
I gain

×

10.

MD4

An analog voltage input is used as the feed-back signal.
I gain

×

10.

4 3

F

Notes:

• If the target value signal is to be entered to an external terminal, the signal

should not be assigned to the terminal used by the feed-back signal input. If
assigned, no PID operation is possible.

• The [PID LVL] value (0 to 200%) corresponds to 0 to 10V of analog voltage

input. In other words, if the target value input of 5V is converted to an inter-
nal level, set 100% for the [PID LVL].

• If target values are to be entered with current (OI-L input), turn on the AT

terminal.