beautypg.com

Hitachi J300U Series User Manual

Page 86

background image

10-5

Inspection cycle

Inspection
location

Inspection item

Inspection content

Inspection method

Criteria

Standard
replacement
period

Instruments

Regularly Periodic

Control
circuit

Operation check

(1) Check the balance of the
output voltage of
individual phases when
operating the inverter
independently.

(2) Conduct a sequence
protection operation test,
and make sure that there
are no errors in the protec-
tion and display circuits.

(1) Measure the
voltage between
the phases of
inverter output
terminals U, V,
and W.

(2) Simulate
operation of the
inverter protect-
ion circuit.

(1) Within 2% voltage
difference between
phases.

(2) Operate without any
abnormalities.

___

__

Compo-
nent
check,
including
printed-
circuit
boards

Overall

(1) No abnormal odor or
changes in color.

(2) No significant corrosion.

Visual inspection

No abnormalities

___

Capacitor No fluid leakage or

deformation.

Visual inspection

5 years
(Note 1)

___

Display

Digital operation
panel

(1) No illegible display

(2) No lack of character

(3) No blown out LEDs

Visual inspection

Normal operation

Display can be read out.

7 years

___

___

No abnormalities

Note 1. The life of the capacitor is affected by the ambient temperature. Refer to the ambient temperature - capaciitor life curve shown in Appendix 5.
Note 2. The inverter must be cleaned periodically. If dust accumulates on the fan and heat sink, it can cause overheating of the inverter.

Daily Inspection and Periodic Inspection (3/3)