For error contents, see page 8-1. other displays, Digital operator dop, drw display – Hitachi J300U Series User Manual

Page 107

background image

12-16

12.4

Protection function display list when the remote operator is used

There are protection functions for overcurrent, overvoltage, and undervoltage provided to
protect the inverter. When one of the functions is performed, the output is cut off, and the
motor is put into the free run state, and the status is kept until the inverter is forced to reset.

Constant speed

Name

Digital operator display

Remote operator(DOP)
copy unit(DRW)display

ERR1 ✽ ✽ ✽ ✽

Overload
protection

Name

Digital operator display

Remote operator(DOP)
copy unit(DRW)display

ERR1 ✽ ✽ ✽ ✽

Overcurrent
protection

Deceleration

Acceleration

Braking resistor
overload
Overvoltage
protection

EEPROM error

Undervoltage
protection

CT error

CPU error

External trip

USP error

Input overvoltage

Instantaneous
power failure

Option connec-
tion error

Option 1

Option 2

Option 1

Option 2

Option PCB
error
(NOTE 2)

Undervoltage
standby

Phase failure
protection error

Power module
protection

Constant speed

Deceleration

Acceleration

OC.Drive

OC.Decel

OC.Accel

Over.L

OL.BRD

Over.V

EEPROM

Under.V

CT

CPU

EXTERNAL

USP

Stop

OV.SRC

Inst.P-F

NG.OP1

NG.OP2

OP1

OP2

UV.WAIT

PH.Fail

PM.Drive

PM.Decel

PM.Accel

PM.ERR

Display

For error contents, see page 8-1.

Other displays

Description

Cause

Communication error
*=1. Protocol error
=2. Time-out error

This is displayed when an error occurs between the inverter and remote operator.
When the STOP key or another key is pressed, the original display appears.
When the original display does not appear, turn the power off and then on once
again. Check whether any connectors are loose.

During inverter running

If one of the displays on the left occurs when the copy unit is used to read or copy,
take the corresponding countermeasure.
• INV. RUN: Stop the running.
• INV. TRIP: Press the STOP key to release the trip.
• INV. TYPE: The inverter type of the copy source is different from that of the
copy destination. Use the same type of inverter to read or copy.

Under inverter trip

Inverter type mismatch

Inverter read lock

The fourth switch of the DIP switch on the back of the remote operator is ON.
When reading data, turn the switch OFF.

Instantaneous power
failure restart function in
operation

This indicates that the instantaneous power failure restart function is being performed.
• RESTART: 0 start is in execution.
• ADJUST: Frequency matching is in execution.

Undervoltage

The supply voltage is lowered to the undervoltage level. When this display
appears, turn the power on once again.

Power OFF

The undervoltage after the power is turned off is displayed.

This is displayed after the autotuning measurement is finished.
• Tuning OK: The measurement terminates normally.
• Tuning NG: The measurement fails.

Autotuning function end
display

R-ERROR COMM<

>

R-ERROR INV.RUN

R-ERROR INV.TRIP

R-ERROR INV.TYPE

R-ERROR RD LOCK

RESTART

✽ ✽ ✽

.

s

UV WAIT

POWER OFF

ADJUST

✽ ✽ ✽

.

s

Tuning OK

Tuning NG

(NOTE 1)

Ground fault
protection

GND.Flt

NOTE 1: Power OFF during motor deceleration may cause an input phase failure error.
NOTE 2: When the J-FB is installed, an error is display for each factor as shown below.

Digital operator

DOP, DRW

display

Encoder line break:
Overspeed:
Positioning error:
Thermistor line break:
Motor overheat:
Malfunction or abnormality on built-in CPU of the option:

OP1 0
OP1 1
OP1 2
OP1 4
OP1 5
OP1 7