7-21

Contents and display

Extension

function

code

1

2

FUNC

FUNC

Dynamic
braking
usage ratio

Initial value

Setting method

Set the usage ratio (%) for 100 seconds of BRD.
When the BRD operation exceeds this setting,
the operation will be stopped.

1

2

.

.

t1

t2

t3

ON

ON

ON

BRD ON

T =

(t1 + t2 + t3)

100 seconds

100 seconds

100

Function contents

NOTE 1:

NOTE 2:

NOTE 3:

NOTE 4:

NOTE 5:

NOTE 6:

The internal BRD circuit is not mounted
in an inverter other than the types 055L/HF,
and 075L/HF.

When 0 % is set, the BRD will not be
operated.

When T exceeds the set value, the BRD
will be stopped.

When mounting an external BRD unit, set

the usage ratio to and remove the

external resistors.

The initial settings of 110-550L/HF
are 0.0%.

Conditions when using the external
resistor are shown in the table.

Model

055, 075HF

RB2, two each in series

(70 ohm or more)

Inverter requiring an external resistor

External

resistor

Usage ratio

Max. 10 (%)

NOTE 7:

This function cannot be used for the inverter types 110 to 550L/HF which have no built-in BRD
(dynamic braking) circuit.

.

Arrival
optional
frequency
at accelera-
tion

Arrival
optional
frequency
at decelera-
tion

1

2

FUNC

Initial value

Setting method

When frequency arrival signal output method 2 is selected, an output signal is outputted

at an optional frequency. When frequency arrival signal output method 1 is selected, an output

signal is outputted at an optional frequency or more. For acceleration and deceleration

, the frequency is set in units of 0.1 Hz (in units of 1 Hz for 100 Hz or more).

➤ ➤

.

1

2

FUNC

Initial value

.

In the case of optional
arrival frequency
of acceleration

In the case of optional
arrival frequency
of deceleration

At the time of acceleration, an output signal
is turned ON in a range from the set frequency
-0.5 Hz to the set frequency +1.5 Hz. At the
time of deceleration, an output signal is turned
ON in a range from the set frequency +0.5 Hz
to the set frequency -1.5 Hz.

Output
frequency

f

Output
signal
(FA1)

Running
time

60 ms

60 ms

0.5 Hz

-1.5 Hz

1.5 Hz

-0.5 Hz

t

0

FUNC

FUNC

ON

➤ ➤

setting

setting

055, 075LF

RB1 to RB3

(17 ohm or more)

Max. 10 (%)