12 5.6 control circuit terminals, 1 to 8 – Hitachi J300U Series User Manual

Page 32

background image

5-12

5.6

Control Circuit Terminals

Forward
Reverse

SWF
SWR

ON

ON

SWR

CM1 PLC P24 FW

8

1

•••••

SWF

ON

ON

ON

ON

ON

ON

ON

CM1

Fourth (FS)

speed

Third

speed

Second

speed

First

speed

Frequency

(Hz)

Switch
SW1
SW2
SWF

Time

PLC P24 FW 8

7

6

SWF

SW1 SW2

(Source type)

• When setting frequency,

connect P24 and 6 or 7
and set with digital
operator or .

1

2

1 to 8

Terminal symbol

Terminal name

Description

FM

Monitor terminal

Analog: Output frequency, current, torque

Digital: Output frequency x frequency converted value
(Set in the remote operator monitor mode), max. pulse: 3.6 kHz

CM1

Common terminal 1

Common terminal for the monitor terminal

PLC

Internal

interface

common

Common terminal for the external power source of the sequencer

P24

Input signal power source

Internal power source for the contact input terminal and frequency
monitor terminal, 24 VDC.
Common for the FW terminal and intelligent input terminals

FW

Forward

run/stop

terminal

OUTPUT frequency

REV

Reverse run/stop

CF1

SW1

CF2

Multistage speed

SW2

CF3

SW3

(NOTE 1)

JG

Jogging

Jogging run

DB

External DC braking

DC braking input signal

STN

Initialization

Initialization (shipment status at factory) input

SET

2nd function

The output frequency setting, base and maximum frequencies,

control method, motor constant, acceleration or deceleration time,
manual torque boost setting, and electronic thermal setting are
changed in batch.

CH1

Two-stage acceleration

The acceleration or deceleration time or selection of two-stage

or deceleration

accration or deceleration is changed by turning the contact ON.

FRS

Free run stop

The inverter stops and the motor stops free run

FRS functions when the contact is opened. (European version)

EXT

External trip

External trip input signal (The contact is open.)

USP

Power-ON restart

Restart prevention when the power is turned on in the RUN

prevention

state (The contact is open.)

CS

Commercial power source

Switch signal from the commercial power source to inverter

switching

drive (Note: When the terminal is used, a trip is also conceled.)

SFT

Terminal software lock

The data of all funcitons except for output frequency setting is

locked. See 12-9 [F-25].

AT

Analog input command

Analog input voltage-current switching (When the contact is ON,
current input signal to OI-L is acrive.)

RS

Reset

Trip or alarm signal is reset.

UP

Remote control function,

When the contact is turned ON, the operation is accelerated.

acceleration

(Available only when the frequency command is sent

to the operator.)

DWN

Remote control function,

When the contact is turned ON, the operation is decelerated.

deceleration

(Available the frequency command is sent to the operator.)