10-3

Daily Inspection and Periodic Inspection (1/3)

Inspection cycle

Inspection
location

Inspection item

Inspection content

Inspection method

Criteria

Standard
replacement
period

Instruments

Daily Periodic

Overall

Ambient
environment

Check ambient temperature,
humidity, dust, corrosive
gases, oil mist, etc.

Ambient temperature
between -10 to +50˚C;
no icing.

Thermometer

__

Devices overall

Check for abnormal
vibrations and noise.

Visual and aural
inspection.

Ambient humidity 20 to
90%; no dew condensation.

Hygrometer

Power supply
voltage

Check the input line voltage.

Measure the voltage
between inverter
terminals R(L1),
S(L2) and T(L3).

No abnormalities.
200 to 220 V, 50 Hz
200 to 230 V, 60 Hz
380 to 415 V, 50 Hz
400 to 460 V, 60 Hz

Tester

Main
circuit

Overall

(1) Insulation resistance test
(between main circuit
terminals and grounding
terminal)

(2) Check installation for
looseness.

(3) Check for evidence of
overheating in the various
components.

(4) Clean.

No abnormalities in (1) and
(2).

Tightening torque (kgf.cm)
• M3: 8 - 10
• M4: 12 - 15
• M5: 20 - 25
• M6: 25 - 30
• M8: 100 - 135
• M10: 150 - 200

Tightening torque for IPM
and Diode modules
(kgf.cm)
• M4: 10-15
• M5: 15-20
• M6: 20-25

__

500 V class
Megohm meter

(2) Tighten.

(3) Visual
inspection.

(1) Increase tighting
Making a check
on the terque is
needed for the
increase tighten-
ing of the modules
such as a power
module, diode
module. Do not
execute increse
tightening with
no torque gauge
prepared.