Contact specification – Hitachi J300U Series User Manual

Page 39

background image

6-5

• The failure alarm signal is generated from the terminal AL0 and AL1 when a failure hap-

pens. At this time the contents of the failure are displayed on the digital operator.

• Whether the alarm terminal output is to be turned on or off during normal run can be

selected by the extension function

.

The alarm output terminals at initial setting are as follows (1).

The alarm output terminals are valiable as follows (2) by setting

.

Operation

Status

(1) Contact b

(2) Contact a

During normal operation

At occurrence of an

alarm or power off

During normal operation

or at power off

At occurrence of an alarm

Contact Power Operation

Status

AL0-AL1

AL0-AL2

b

(initial

setting)

ON
ON

OFF

Normal

Closed

Open

Abnormal

Open

Closed

Ñ

Open

Closed

Contact Power

AL0-AL1

AL0-AL2

a

ON
ON

OFF

Normal

Open

Closed

Abnormal

Closed

Open

Open

Closed

AL2

AL1

AL0

AL2

AL1

AL0

AL2

AL1

AL0

AL2

AL1

AL0

Ñ

• Contact specification

250 VAC 2.5 A (Resistor load) 0.2 A (cos

¿

=0.4)

100 VAC 10 mA

30 VDC 3.0 A (Resistor load) 0.7 A (cos

¿

=0.4)

5 VDC 100 mA

Minimum

Maximum

Working voltage: Max. 50 V

• Saving the alarm signal

When an alarm signal is outputted, the alarm signal data is stored even if the input power is
turned off and the contents can be checked by turning the power on once again. However,
when the input power is turned off, the inverter control power is also turned off. As a
result, when the power is turned on next, the alarm contact output is reset (deleted). There-
fore, when saving the alarm contact output, let the external sequence receive and save it
and then turn off the inverter input power.

• When the alarm contact output is set ON during normal run, a time delay occurs until the

contact is closed when the power is turned on. Therefore, when using the alarm contact
output, set a time delay of about 2 seconds when the power is turned on.