Hitachi J300U Series User Manual

Page 100

background image

12-9

NOTE 1: When MD0 is set and the input terminal SFT is turned ON, the data of all functions is locked. When MD2 is

set (stored), the data of all the functions is locked. During locking, no data can be changed. MD1, MD3
can set only the output frequency.

NOTE 2: Electronic thermal characteristic free setting current and frequency depends on the inverter rating.

Display

(Function mode 1)

(Function mode 2)

Setting, change

sequence

Function

Function

Initialization display

Initialization

contents

Setting contents

No.

name

contents

16

F-23

Electronic

E-THM A1

8.5A

Rated capacity of

0 to 600.0 A

Electronic thermal

each inverter

thermal

characteristic

(NOTE 2) free setting

current (1)
Electronic

E-THM F1 0000 Hz

Rated capacity of

0 to 400 Hz

thermal

each inverter

characteristic
free setting
frequency (1)
Electronic

E-THM A2

8.5A

Rated capacity of

0 to 600.0 A

thermal

each inverter

charac teristic
free setting
current (2)
Electronic

E-THM F2

5 Hz

Rated capacity of

0 to 400 Hz

thermal

each inverter

characteristic
free setting
frequency (2)
Electronic

E-THM A3

13.0 A

Rated capacity of

0 to 600.0 A

thermal

each inverter

characteristic
free setting
current (3)
Electronic

E-THM F3

73 Hz

Rated capacity of

0 to 400 Hz

thermal

each inverter

characteristic
free setting
frequency (3)

17

F-24

Overload

OLOAD LEVEL125%

125%

50 to 150%

Under the sensorless vector

Overload

restriction

control, an overload is detected

restriction level setting

from both the overload restric-

tion and torque limiter.

Overload

OLOAD CONST01.0

1.0

0.3 to 31.0

When the setting is 31.0 in SLV

restriction

or V2 control mode, the

constant

overload restriction has no

setting

effect.

Valid

OLOAD ACC

ON

ON

ON: Valid for

Even if the function is set to

selection

acceleration

OFF, the overload restriction is

for overload

Keep the

invalid only for the first

restriction

function ON

acceleration when the forward

acceleration

for operation.

and reverse run command is
turned on.

18

F-25

Software

S-LOCK

MD1

MD1

MD0/MD1

MD0, MD1: Terminal software

lock

MD2/MD3

lock (SFT)

selection

MD2, MD3: Software lock
(NOTE 1)