beautypg.com

Wiring components, Load distribution wire sizes and lugs selection, Wiring – Emerson SAG581126000 User Manual

Page 81: Components

background image

System Application Guide

SAG581126000

Spec. No. 581126000 (Model 700

NVBA

)

Issue AD, November 23, 2009

Page 81 of 123

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Wiring Components

Load Distribution Wire Sizes and Lugs Selection

Features

When Distribution Bus Modules Using Bullet Nose-Type Devices (TPS/TLS Fuses and/or Bullet

Nose-Type Circuit Breakers) are Provided: Lug-terminated load leads are connected to the individual
load busbars located on the Distribution Bus Module and the respective distribution ground busbar.

The individual load busbars provide 1/4-20 threaded holes for installation of customer-provided two-hole
lugs that have 5/8 inch centers and 1/4 inch bolt clearance holes. Customer must provide lug mounting
bolts and hardware.

The distribution ground busbar provides 1/4-20 studs for installation of the same type of customer-
provided lugs. Customer must provide lug mounting hardware.

Refer to the illustrations under the

LIST DESCRIPTIONS

for a dimensional drawing.

Maximum size of wire to be connected to a single fuseholder/circuit breaker position is 2 AWG. For wiring
up to 350 kcmil, see

Table 11 (Special Application Crimp Lug / Strap Combination)

, or see the following

part numbers in

ACCESSORY DESCRIPTIONS

for available adapter busbars:

514717

,

534449

, and

514714

.

When Distribution Bus Modules Using GJ/218 Circuit Breakers or TPH Fuses are Provided: Lug-

terminated load leads are connected to the individual load busbars located on the Distribution Bus
Module and the respective distribution ground busbar.

The individual load busbars provide 3/8-16 captive nuts for installation of customer-provided two-hole lugs
that have 1 inch centers and 3/8 inch bolt clearance holes. Customer must provide lug mounting bolts
and hardware.

The distribution ground busbar provides 3/8-16 captive nuts for installation of the same type of customer-
provided lugs. Customer must provide lug mounting bolts and hardware.

Refer to the illustrations under the

LIST DESCRIPTIONS

for a dimensional drawing.

Restrictions

See 'Features' above.

Ordering Notes

1) The rating of the distribution device determines the load lead wire size requirement. The Distribution Bus

Module ordered determines the lug hole size and spacing requirements. For wire size and lug selection;
refer to the following.

a) When Distribution Bus Modules Using Bullet Nose-Type Devices (TPS/TLS Fuses and/or Bullet

Nose-Type Circuit Breakers) are Provided: The individual load busbars and associated ground
busbar are designed to accommodate the lugs listed in Tables

9

and

11

. Use Table

12

to select

recommended load distribution wire sizes and lugs for various loop lengths per fuse/circuit breaker
ampere rating.

b) When Distribution Bus Modules Using GJ/218 Circuit Breakers or TPH Fuses are Provided:

The individual load busbars and associated ground busbar are designed to accommodate the lugs
listed in Table

10

. Use Table

13

to select recommended load distribution wire sizes and lugs for

various loop lengths per fuse/circuit breaker ampere rating.

2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.