List RA: 1200A Low Voltage Battery Disconnect (LVBD)
Contactor and Control Circuit (P/N 540808)

Features

♦ Provides a battery disconnect contactor, which is mounted in bus position A (row 1) of the Distribution

Cabinet.

Restrictions

Limit one bus arrangement of this type per System.

Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.

Cannot be used with List 92, 93, RB, RC, RD, or RE.

Ordering Notes

1) Order as required.

2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table

10

.

1"

1-1/4"

1-1/4"

BATTERY

(LOAD SIDE)

CONNECTIONS

CLEARANCE HOLES FOR 3/8 BOLT, 2 PLACES
FOR MOUNTING LUG ON BACK SIDE OF BUSBAR
(CUSTOMER MUST PROVIDE LUG BOLTS, NUTS AND
ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

3/8-16 CAPTIVE NUT, 4 PLACES
(CUSTOMER MUST PROVIDE LUG
BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")